主な機能

  • Revenue grade power metering +/- 2%
  • 0 to 10 V dimming control
  • Motion detection input
  • Distributed intelligence - no need for gateway to be on line for set up
  • Custom zero crossing circuit for inrush current protection
  • AES 128 bit encryption
  • Data logging
  • Failure detection and reporting
  • Photocell thresholds synchronization
  • Motion detector input
  • Emergency call button input
  • Over the air flashing (program updates)

Tech Specs

Wireless Specifications
  • Wireless standard:IEEE 802.15.4
  • Operating frequency:902-928 MHz
  • Channels:10
  • RF power:adjustable to +24 dBm (250 mW)
  • Antenna:internal/external 1/4 wave monopole
  • Range:gateway base to TOP900 = 2 miles (LOS)
  • Range:TOP 900 to TOP900 @ 25’ AGL (LOS) 1 mile
Electrical Specifications
  • Connects to new ANSI 136.41 connector
  • 345J surge protection
  • Operating voltage:120 –277 VAC, 50/60 Hz
  • Operating temperature: -40 °C to +70 °C
  • Fixture power contact:1000 W, 10 A
Low Voltage Control Wiring
  • Violet + 0-10 V (Sink)
  • Gray - 0-10 V (Ground)
  • Orange +12 V DC for Motion Sensor
  • Brown Motion Detector input
Line Voltage Wiring
  • Line L1 (Black)
  • Common L2 (White)
  • Switched Power (Red)
Warranty