主な機能

  • High-performance, low-cost; Cuts control network installation time and cost
  • Flexible power input:9–28Vac and 9–35Vdc
  • DIN rail, wall, or panel mount
  • Channel access through front panel phone jacks; Includes local status display LEDs and remotely reports status and faults
  • Intelligent repeater mode
  • MPR-50 routers can be installed by any standard LonWorks® network commissioning tool including the LonMaker® Integration Tool.Custom shapes are available for the LonMaker tool that simplify installation of MPR-50 routers.

Tech Specs

  • Router 1 Transceiver TP/XF-1250 (LONMARK standard channel type)
    Router 2-5 Transceiver TP/FT-10 (ANSI/CEA-709.3 and LONMARK standard channel type);
    link power compatible
    Network Connectors
    Permanent Captive, screw terminals
    Convenience Front panel-mounted 3.5mm mono phone jacks; compatible with PCC-10 PC Card and
    U10 USB Network Interface cable accessorieswww.echelon.com
    Copyright © 2005-2007, Echelon Corporation.Echelon, LON, LONWORKS, LONMARK, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, LonPoint, Digital Home, Neuron, 3120, 3150, LNS, i.LON, LONWORLD, ShortStack,
    Panoramix, Panoramix Powered by Echelon, LonMaker, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries.Pyxos, LonLink, LonResponse,
    LonSupport, LONews, Open Systems Alliance, OpenLDV, LonBridge, Powered by Echelon, LNS Powered by Echelon, LONWORKS Powered by Echelon, Networked Energy Services Powered by Echelon, NES Powered by
    Echelon, and Thinking Inside the Box are trademarks of Echelon Corporation.Other trademarks belong to their respective holders.
    Disclaimer
    Neuron Chips, Free Topology Twisted Pair Transceiver Modules, and other OEM Products were not designed for use in equipment or systems which involve danger to human health or safety or a risk of property damage and
    Echelon assumes no responsibility or liability for use of the Neuron Chips or Free Topology Twisted Pair Transceiver Modules in such applications.ECHELON MAKES AND YOU RECEIVE NO WARRANTIES OR CONDITIONS,
    EXPRESS, IMPLIED, STATUTORY OR IN ANY COMMUNICATION WITH YOU, AND ECHELON SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
    PURPOSE.003-0402-01C
    Service Switches Six, recessed and finger-accessible
    Operating Input Voltage 9-28VAC 40-70Hz, 9-35VDC
    Operating Input Current 500mA maximum
    LED Indicators Power (one—green), Status (six—green, yellow or amber);
    Status LED legend on front panel
    Temperature
    Operating 0 to +70° C
    Non-operating -20° to +85° C
    Humidity
    Operating (non-condensing) 25 to 90% RH @ +50° C
    Non-operating (non-condensing) 95% RH @ +70° C
    Shock and Vibration ETSI300 019-2-3 T3.2
    Dimensions 157.5mm (9 TE) wide, 80mm high, 80mm deep
    EMC FCC Part 15 Level B, EN55022 Class B, EN55024, CISPR 22 Class B, VCCI Class B
    Agency Listings U.L. 60950, cU.L.C22.2 No. 60950-00, TÜV EN60950, CE, C-Tick